IMJ00503 V3E.DOC Page 25 of 40 19.02.2009
Fig. 6: Digital switching output behaviour for positive and negative hysteresis.
LOW corresponds to a voltage level < 2 V.
HIGH corresponds to a voltage level of VCC 2 V.
Each alarm output is short circuit proof and rated for a maximum current load of 0.5 A.
Parameter settings for alarm outputs can be made with the Profibus master, using the Encoder
profile with Class 1 functionality.
The following parameters may be configured (refer to GSD File):
ExtUserPrmData = 29
“Sw
itching point output 1 (31 16)” for AC alarm output 1
ExtUserPrmData = 30
“Switching point output 1 (15
0)” for AC alarm output 1
ExtUserPrmData = 31
“Switching point output 2 (31
16)” for AC alarm output 2
ExtUserPrmData = 32
“Swi
tching point output 2 (15 0)” for AC alarm output 2
ExtUserPrmData = 33
“Hysteresis output 1 (31
16)” for AH alarm hysteresis 1
ExtUserPrmData = 34
“Hysteresis output 1 (15
0)” for AH alarm hysteresis 1
ExtUserPrmData = 35
“Hysteresis output 2 (31
16)” for AH alarm hysteresis 2
ExtUserPrmData = 36
“Hysteresis output 2 (15
0)” for AH alarm hysteresis 2
Further switching functionalities, for example, monitoring for specified operating ranges may be
accomplished by combining the two alarm outputs.